Customization: | Available |
---|---|
Certification: | CE, RoHS, MSDS |
Warranty: | 3 Years |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
self-detect
constant power emergency output
Suits for LED fitting with external LED driver
External battery, Li-ion/Li-FePO4/Ni-CD
With multi-protection function;
battery overcharge protection;
battery over-discharge protection;
output overload protection;
short-circuit protection.
Accessary test switch and LED indicator
In the state of the power off, to connect with the battery, static current at the battery terminal is 0uA
Input voltage | 220-240Vac, 50/60Hz |
Input current | 0.003A Max. @230Vac |
Input wattage | <5.0W |
Power factor | ≥0.5 @230 Vac |
Battery charging | 350mA Max. |
Battery charging time | ≤24Max |
Emergency output Voltage
|
DC25-185VMax.200VDC |
Emergency power
|
3W
|
Emergency time
|
3H
|
Battery | Li-FePO4/26650/4000mAh-3.2V |
Storage Temperature | -20-40ºC |
Electric Strength | 3000Vac, 5mA (input to output) |
IP Rating | IP 20 |
Maximum shell temperature | 75ºC |
Warranty | 3 Years |
Relevant standard | IEC 61347-2-7 / IEC 61347-1 / EN55015 |
AC Input: Brown (Line) and Blue (Neutral) wires for 220-240V power supply
LED Connection: Red (positive) and Black (negative) terminals for LED output
Battery: Dedicated charging wires (color not specified) for Li-FePO4 battery connection
Switch Control: Includes wall switch integration
Wire Specs: Uses 0.5-1.5mm² cables with 7-8mm stripping length
LED INDICATOR
Green breathing pattern: charging mode
Green stable: battery fully charged
Red flashing: failure as below
Red flashing Once per second: Battery is not connected
Battery is defective
Red flashing four times a second: Load failure during emergency mode, open circuit/short circuit
TEST BUTTON
1: 0S<Key≤2S, Enter a simulated state of emergency, the green indicator blinks once every second, keep emergency status for 10±1 seconds and back to normal status
2: In simulated emergency situations, Short press once to exit and return to the normal charging state
3: 0S<Key≤1S. In the emergency state, the emergency state is turned off.
QUARTERLY SELF-TEST
when emergency driver is on power, every 180 days±1 day automatically enter the emergency state, emergency duration until the battery is discharged, then return to power-on status.
Application:
school,hospital,subway,train station,shoppingmall,supermarket,airport,office, factory,hotel,basement,parking lot,public place